Product Specifications
|
Specification |
121K6423(NC) |
122K8321(NO) |
|
|
Brand |
Parker Lucifer |
✅ |
✅ |
|
Valve Type |
2/2 Way, Direct Acting |
✅ |
✅ |
|
Function |
Normally Closed / Normally Open |
Power off to shut down, power on to start up |
Power off to conduct, power on to disconnect |
|
Port |
G1/4" BSPP Female |
✅ |
✅ |
|
Orifice |
Orifice |
3.0 mm |
2.5 mm |
|
Kv Value |
Flow Coefficient |
4.5 L/min |
3.5 L/min |
|
Pressure |
Working Pressure |
0–30 bar |
0–30 bar |
|
Media Temp |
Media Temperature |
-30℃ ~ +160℃ |
-30℃ ~ +160℃ |
|
Ambient Temp |
Ambient Temperature |
0℃ ~ 60℃ |
0℃ ~ 60℃ |
|
Body |
Brass CW617N |
✅ |
✅ |
|
Seal |
Ruby Seat |
✅ |
✅ |
|
Coil |
483824, 19W |
✅ |
✅ |
|
Insulation Class |
Class H (180℃) |
✅ |
✅ |
|
Protection |
IP67 / IP44 Optional |
✅ |
✅ |
|
Duty Cycle |
100% Continuous Duty |
✅ |
✅ |
|
Media |
Fuel oil, light oil, heavy oil, lube oil, neutral gas |
✅ |
✅ |
|
Certification |
TÜV DIN CERTCO, EN264/EN267/TRD411 |
✅ |
✅ |

Product Advantages
1. Two models available in one series: 121K6423 NC and 122K8321 NO, to match different safety circuit logic
2. Direct acting design, operates at 0 bar differential pressure, stable performance for low-pressure oil lines
3. Ruby hard seal, high temperature and fuel corrosion resistance, longer service life than normal rubber seals
4. Built-in filter inside valve, block particles to avoid sticking and internal leakage
5. 360° rotatable coil housing, suitable for compact installation in engine room and boiler cabinet
6. Shared coil 483824, 19W, unified spare parts for easy stock management
7. TÜV burner safety certification, direct replacement for Riello, Weishaupt and other imported burner valves
8. Modular construction, seal service kit replaceable separately to save maintenance cost
Working Principle
Both are direct-acting 2/2-way solenoid valves. The coil generates magnetic force to drive the armature when energized, and spring resets after power off.
✅ Cat.No 121K6423 NC: Spring closes the valve when de-energized; magnetic force lifts the armature to open flow when energized. Mainly for safety shut-off, auto fuel cut once power loss.
✅ Cat.No 122K8321 NO: Spring keeps valve open for flow when de-energized; magnetic force closes valve to cut flow when energized. Suitable for bypass and energized-shutdown interlock circuits.
Direct acting without pilot structure, no required differential pressure, stable operation under low pressure.
Application Scenarios
Fuel line on-off and safety protection for oil burners and atomizing burners
Fuel pipeline control for industrial steam boilers and heating systems
Automatic fuel & lube oil control in marine engine room
Neutral gas and compressed air circuit control
Fluid interlock for thermal and petroleum equipment
Replacement spare parts for imported burners (Riello, Weishaupt, Oilon etc.)
Maintenance Instructions
1. Flush pipeline thoroughly before installation, install upstream strainer to protect ruby sealing surface
2. Regularly check coil temperature, terminals and cable gland to prevent moisture ingress
3. Inspect carbon and coke deposits on seat before restart after long idle period, clean if necessary
4. Clean with fuel-compatible solvent; do not scratch ruby disc with hard tools
5. Never remove coil while energized; avoid rapid cycling to prevent coil overheating
6. Check O-ring aging regularly, replace seal service kit as needed
Spare Parts & Accessories
Universal coil 483824 (19W, voltage suffix P8/T1/2P/Q9), seal service kit (ruby disc, O-rings, spring, armature assembly), coil housing, DIN43650 connector, cable gland, upstream strainer
Acceptance Standard
1. Verify model (121K6423 /122K8321), coil voltage and power match purchase order
2. Visual check: brass body free of porosity and cracks, intact threads and protective plugs
3. Function test: NC/NO logic matches model, smooth action without sticking or abnormal noise
4. Pressure holding test: no external leakage, no internal leakage at sealed status
5. Coil insulation resistance qualified, good protection sealing
6. Original packing, certificate and TÜV documents available for verification
Key Highlights
Classic Parker Lucifer K series, 121K6423 NC & 122K8321 NO sold together, one-stop solution for two kinds of burner safety circuit logic. Durable ruby hard seal, zero differential start, fast response. Interchangeable coil for easy stock. TÜV certified, popular replacement parts for marine, boiler maintenance and burner supply trade.
FAQ
Q1:What is the main difference between 121K6423 and 122K8321?
A1:121K6423 is NC (close on power loss), ideal for safety shut-off. 122K8321 is NO (open on power loss), for energized-shutdown interlock. They share same coil but different orifice and Kv flow rate.
Q2:Does it need pressure differential to open?
A2:No, direct acting design works at 0 bar differential pressure, suitable for low-pressure oil lines.
Q3:What coil voltage options are available?
A3:Common T1=230V, P8=115V. Confirm voltage suffix before order.
Q4:Can the coil be interchanged between two models?
A4:Yes, same coil part No.483824, 19W, just match voltage.