| Supply voltage at the detector terminals(Vdc): |
- OLC 100:340 mA (current supply)
- OLCT 100 XP HT:15.5V to 32V
- OLCT 100 XP LEL: 15.5V to 32V
- OLCT 100 XP IR: 13.5V to 32V
- OLCT 100 XP EC: 11V to 32V
- OLCT 100 XP SC: 15.5V to 32V
|
| Average consumption: |
- OLC 100: 340 mA
- OLCT 100 XP HT: 100 mA
- OLCT 100 XP LEL: 110 mA
- OLCT 100 XP IR: 80 mA
- OLCT 100 XP EC: 23.5mA
- OLCT 100 XP SC: 100 mA
|
| Output current(signal): |
- Current source encoded from 0 to 23 mA(non isolated)
- Linear 4 to 20 mA current reserved for measurement
- 0mA: electronic fault or no power supply
- <1 mA: fault
- 2 mA: initialization mode
- frozen to 20 mA: the concentration of combustible gas has
reached 100%LEL
|
| Type of cable: |
- Explosimeter: screened, 3 active wires
- HT Explosimeter: screened, 3 active wires
- Electrochemica detector: screened, 2 active wires
- Infra-red detector : screened, 3 active wires
- Semiconductor detector: screened, 3 active wires
|
| Cable inlet: |
M20 x 1.5(cable gland not suppled) or 3/4 NPT |
| Maximum diameter of cable entering the detector: |
12 mm |
| Electromagnetic compatibility: |
Conforms to EN50270:06 (typ2) |
| Ingress Protection: |
IP66 |
| Weight: |
- OLC 100: 0.95 kg
- OLCT 100 XP HT: 1.8 kg
- OLCT 100 XP LEL: 1.0 kg
- OLCT 100 XP IR: 1.1 kg
- OLCT 100 XP EC: 1.1 kg
- OLCT 100 XP SC: 1.1 kg
|
| Materials: |
Epoxy painted aluminum.316 Stainless Steel in option |